Toshiba VF-FS1 Power Supply User Manual


 
E6581381
M-7
13
13.4 How to determine the causes of other problems
The following table provides a listing of other problems, their possible causes and remedies.
Problems Causes and remedies
The motor runs in the
wrong direction.
Invert the phases of the output terminals U, V and W.
Invert the forward/reverse run-signal terminals of the external input device.
See section 6.3 "Assignment of functions to control terminals".
Change the setting of the parameter HT in the case of panel operation.
The motor runs but its
speed does not change
normally.
The load is too heavy. Reduce the load.
The soft stall function is activated. Disable the soft stall function. See section 5.12.
The maximum frequency HJ and the upper limit frequency WN are set too low.
Increase the maximum frequency HJ and the upper limit frequency WN.
The frequency setting signal is too low. Check the signal set value, circuit, cables, etc.
Check the setting characteristics (point 1 and point 2 settings) of the frequency setting
signal parameters.
See section 6.5.
If the motor runs at a low speed, check to see that the stall prevention function is
activated because the torque boost amount is too large.
Adjust the torque boost amount (XD) and the acceleration time (CEE).
See section 5.11 and 5.1.
The motor does not
ac-celerate or decelerate
smoothly.
The acceleration time (CEE) or the deceleration time (FGE) is set too short.
Increase the acceleration time (CEE) or the deceleration time (FGE).
A too large current flows
into the motor.
The load is too heavy. Reduce the load.
If the motor runs at a low speed, check whether the torque boost amount is too large.
See section 5.11.
The motor runs at a higher
or lower speed than the
specified one.
The motor has an improper voltage rating. Use a motor with a proper voltage rating.
The motor terminal voltage is too low.
Check the setting of the base frequency voltage parameter (XNX) .
See section 6.12.5.
Replace the cable with a cable larger in diameter.
The reduction gear ratio, etc., are not set properly. Adjust the reduction gear ratio, etc.
The output frequency is not set correctly. Check the output frequency range.
Adjust the base frequency. See section 5.9.
The motor speed fluctu-ates
during operation.
The load is too heavy or too light. Reduce the load fluctuation.
The inverter or motor used does not have a rating large enough to drive the load.
Use an inverter or motor with a rating large enough.
Check whether the frequency setting signal changes.
If the V/F control selection parameter RV is set at , check the vector control setting,
operation conditions, etc. See section 5.10.
Parameter settings cannot
be changed.
Change the setting of the parameter H (prohibition of change of parameter
setting) to (permitted) if it is set at (prohibited).
* For reasons of safety, some parameters cannot be reprogrammed while the inverter is
running. See section 4.2.6.
How to cope with parameter setting-related problems
If you forget parameters
which have been reset
You can search for all reset parameters and change their settings.
See section 4.2.3 for details.
If you want to return all
reset parameters to their
respective default settings
You can return all parameters which have been reset to their default settings.
See section 4.2.7 for details.