Toshiba VF-FS1 Power Supply User Manual


 
E6581381
F-18
6
6.5.3 Setting of frequency with the input from an external
contact
H : External contact input - UP response time
H
: External contact input - UP frequency steps
H
: External contact input - DOWN response time
H
: External contact input - DOWN frequency steps
H
: Initial up/down frequency
H
: Change of the initial up/down frequency
Function
These parameters are used to set an output frequency by means of a signal from an external device.
Title Function Adjustment range Default setting
H
External contact input - UP response
time
0.0 - 10.0 (s) 0.1
H
External contact input - UP frequency
steps
0.0 - FH (Hz) 0.1
H
External contact input - DOWN
response time
0.0 - 10.0 (s) 0.1
H
External contact input - DOWN
frequency steps
0.0 - FH (Hz) 0.1
H Initial up/down frequency LL - UL (Hz) 0.0
H
Change of the initial up/down
frequency
0: Not changed
1: Setting of
H changed
when power is turned off
1
* These functions take effect when parameter HOQF (frequency setting mode selection 1) is set to or
parameter
H (frequency setting mode selection 2) is set to is enabled.
Adjustment with continuous signals (Parameter-setting example 1)
Set parameters as follows to adjust the output frequency up or down in proportion to the frequency
adjustment signal input time:
Panel frequency incremental gradient =
H/H setting time
Panel frequency decremental gradient =
H/H setting time
Set parameters as follows to adjust the output frequency up or down almost in synchronization with the
adjustment by the panel frequency command:
H = H = 1
(
HJ/CEE (or H)) (H/H setting time)
(
HJ/FGE (or H)) (H/H setting time)