E6581381
E-16
5
5.7 Maximum frequency
HJ: Maximum frequency
• Function
1) Programs the range of frequencies output by the inverter (maximum output values).
2) This frequency is used as the reference for acceleration/deceleration time.
Output frequency
(Hz)
When HJ
=80Hz
When HJ=60Hz
80Hz
60Hz
0 100% Frequency setting signal (%)
This function determines the value
in line with the ratings of the motor
and load.
Maximum frequency cannot be
adjusted during operation.To
adjust, first stop the inverter.
+ If HJ is increased, adjust the upper limit frequency WN as necessary.
[Parameter setting]
Title Function Adjustment range Default setting
HJ
Maximum frequency 30.0-200.0 (Hz) 80.0
5.8 Upper limit and lower limit frequencies
WN: Upper limit frequency
NN
: Lower limit frequency
• Function
Programs the lower limit frequency that determines the lower limit of the output frequency and the upper
limit frequency that determines the upper limit of that frequency.
0 100%
Output frequency (Hz)
WN
HJ
Frequency setting signal
* Frequencies that go
higher than
WN
will not
be output.
Upper limit
frequency
0 100%
Output frequency (Hz)
HJ
NN
Frequency setting signal
* The output frequency
cannot be set at less than
NN
.
Lower limit
frequency