6.14 Conducting PID control
H : PID control waiting time
H
: PID control
H
: Proportional gain
H
: Integral gain
H
: Differential gain
• Function
Using feedback signals (4 to 20mA, 0 to 10V) from a detector, process control can be exercised, for
example, to keep the airflow, amount of flow or pressure constant.
[Parameter setting]
Title Function Adjustment range Default setting
H PID control waiting time 0-2400 [s] 0
H PID control
0: Disabled
1: Enabled (Feedback: VIA)
2: Enabled (Feedback: VIB)
0
H Proportional gain 0.01-100.0 0.30
H Integral gain 0.01-100.0 0.20
H Differential gain 0.00-2.55 0.00
1) External connection