<Frequency setting mode selection>
Title Function Adjustment range Default setting
HOQF Frequency setting mode selection 1
1: VIA
2: VIB
3: Operation panel
4: Serial communication
5: UP/DOWN from external contact
1
[Programmed value]
:
VIA input
A frequency command is set by means of a signal from an external input device
(VIA terminal: 0-10Vdc or 4-20mAdc).
:
VIB input
An external signal (VIB terminal: 0-10Vdc) is used to specify a frequency
command.
:
Operation panel
Press the key or the key on either the operation panel or the
expansion panel (optional) to set frequency.
:
Communication
Frequencies are set by commands from an external control unit.
:
UP/DOWN frequency
Terminals are used to specify an up/down frequency command.
+ No matter what value the command mode selection EOQF and the frequency setting mode selection
HOQF are set to the control input terminal functions described below are always in operative state.
Reset terminal (default setting: RES, valid only for tripping)
Standby terminal (when programmed by programmable input terminal functions).
External input tripping stop terminal command (when so set using the programmable input terminal
function)
+ To make changes in the command mode selection EOQF and the frequency setting mode selection 1
HOQF, first stop the inverter temporarily.
Preset-speed operation
EOQF: Set to (Terminal board).
HOQF: Valid in all setting values.