Toshiba VF-FS1 Power Supply User Manual


 
E6581381
K-4
11
11.3 Extended parameters
Input/output parameters 1
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
H
0100 Low-speed signal
output frequency
Hz 0.1/0.01 0.0-HJ 0.0 6.1.1
H
0101 Speed reach
setting frequency
Hz 0.1/0.01 0.0-HJ 0.0 6.1.3
H
0102 Speed reach
detection band
Hz 0.1/0.01 0.0-HJ 2.5 6.1.2
H
0108 Always active
function selection 1
-
-
0-71 (No function) 0 6.3.1
0: VIA - analog input
1: VIA - contact input (Sink)
H
0109 Analog/contact
input function
selection (VIA
terminal)
--
2: VIA - contact input (Source)
0 6.2.1
H
0110 Always-active
function selection 2
- - 0-71 (ST) 1 6.3.1
H
0111 Input terminal
selection 1 (F)
- - 0-71 (F) 2
H
0112 Input terminal
selection 2 (R)
- - 0-71 (R) 3
H
0113 Input terminal
selection 3 (RES)
- - 0-71 (RES) 10
H
0118
Input terminal
selection 8 (VIA)
--
0-71 (SS1) 6
6.3.2
H
0130
Output terminal
selection 1A
(RY-RC)
--
0-255 (LOW) 4
H
0132 Output terminal
selection 3 (FL)
- - 0-255 (FL) 10
6.3.3
H
0137 Output terminal
selection 1B
(RY-RC)
- - 0-255 (always ON) 255 6.3.4
0: H and H
H
0139 Output terminal
logic selection
(RY-RC)
--
1: H or H
0
H
0167 Frequency
command
agreement
detection range
Hz 0.1/0.01 0.0-HJ 2.5 6.3.5
H
0170 Base frequency 2 Hz 0.1/0.01 25.0-200.0 50.0 (WP)
60.0 (WN)
H
0171 Base frequency
voltage 2
V 1/0.1 50-330 (200V class)
50-660 (400V class)
* 2
H
0172 Torque boost 2 % 0.1/0.1 0.0-30.0 * 1
6.4.1
H
0173 Motor electronic-
thermal protection
level 2
%
(A)
1/1 10-100 100 5.12
6.4.1
H
0185 Stall prevention
level 2
%
(A)
1/1 10-110,
111 (disabled)
110 6.4.1
6.17.2
*1 : Default values vary depending on the capacity. See the table of page K-14.
*2 :