Toshiba VF-FS1 Power Supply User Manual


 
E6581381
K-7
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0: Supply voltage uncorrected, output
voltage limited
1: Supply voltage corrected, output
voltage limited
2: Supply voltage uncorrected, output
voltage unlimited
H
0307 Supply voltage
correction
(limitation of
output voltage)
--
3: Supply voltage corrected, output
voltage unlimited
2 6.12.5
H
0311 Reverse-run
prohibition
- - 0: Forward/reverse run permitted
1: Reverse run prohibited
2: Forward run prohibited
0 6.12.6
H
0312 Random mode - - 0: Disabled
1: Automatic setting
06.11
0: Carrier frequency not reduced
automatically
1: Carrier frequency reduced
automatically
2: Carrier frequency not reduced
automatically
Support for 400V models
H
0316 Carrier frequency
control mode
selection
--
3: Carrier frequency reduced
automatically
Support for 400V models
1
H
0320 Droop gain
1/1 0-100 0 6.13
H
0323 Droop insensitive
torque band
1/1 0-100 10
H
0359 PID control
waiting time
s 1/1 0-2400 0 6.14
H
0360 PID control - - 0: Disabled,
1: Enabled (Feedback: VIA)
2: Enabled (Feedback: VIB)
0
H
0362 Proportional gain - 0.01/0.01 0.01-100.0 0.30
H
0363 Integral gain - 0.01/0.01 0.01-100.0 0.20
H
0366 Differential gain - 0.01/0.01 0.00-2.55 0.00