Toshiba VF-FS1 Power Supply User Manual


 
E6581381
F-76
6
6.20.6 Selection of operation panel stop pattern
H : Selection of operation panel stop pattern
Function
This parameter are used to select a mode in which the motor started by pressing the key on the
operation panel is stopped when the key is pressed.
1) Slowdown stop
The motor slows down to a stop in the deceleration time set with FGE (or H).
2) Coast stop
The inverter cuts off power supply to the motor. The motor comes to a stop after coasting for a while by
inertia. Depending on the load, the motor may keep running for a good long time.
[Parameter setting]
Title Function Adjustment range Default setting
H
Selection of operation panel stop
pattern
0: Slowdown stop
1: Coast stop
0
6.20.7 Display of the head of the parameters
H : Head of the parameter display selection
Function
The parameter can be set at the front of the setting monitor mode.
If selecting “1:CWJ”, the Wizard parameter “CWH” is not displayed.
[Parameter setting]
Title Function Adjustment range Default setting
H
Head of parameter display
selection
0: AUF
1: AUH
0
6.20.8 Integral output power
H : Integral output power retention selection
H
: Integral output power display unit selection
Function
At the main power off ,it is selectable whether retention of integral output power values or not.
And also, the display unit is selectable.
STOP
RUN