E6581381
F-61
6
Title Function Adjustment range Default setting
H
Detection of output short-circuit during
start-up
0: Each time (standard pulse)
1: Only one time after power is
turned on (standard pulse)
2: Each time (short-time pulse)
3: Only one time after power is
turned on (short-time pulse)
0
6.17.9 Over-torque trip
H : Over-torque trip/alarm selection
H
: Over-torque detection level
H
: Over-torque detection time
H
: Over-torque detection level hysteresis
• Function
Use the parameter to trip the inverter or to output the alarm if a torque currrent exceeding the
H-specified level flows for more than the H-specified time. Trip information is displayed
as "QV".
H=: .......... No tripping (FL relay deactivated).
An over-torque alarm can be put out by setting the output terminal function selection
parameter.
H=: .......... The inverter is tripped (FL relay activated) only after a torque current exceeding the
H-specified level has been detected for more than the H-specified time.
Title Function Adjustment range Default setting
H
Over-torque trip/alarm selection
0: Alarm only
1: Tripping
0
H
Over-torque detection level 0-200 (%) 130
H
Over-torque detection time 0.0-10.0 [s] 0.5
H
Over-torque detection level hysteresis 0-100 (%) 10