Toshiba VF-FS1 Power Supply User Manual


 
E6581381
A-20
1
Do not install in any location of high temperature, high humidity,
moisture condensation and freezing and avoid locations where
there is exposure to water and/or where there may be large
amounts of dust, metallic fragments and oil mist.
Do not install in any location where corrosive gases or grinding
fluids are present.
Operate in areas where ambient temperature ranges from -10°C to 60°C.
When installing the inverter where the ambient temperature will rise above 40°C, remove the label
(seal) from the top and operate it at a current lower than the rated one.
5cm
5cm
Measurement position
Measurement position
5cm
Note: The inverter is a heat-emitting body. Make sure proper space and ventilation is provided when
installing in the cabinet. When installing inside a cabinet, we recommend the top seal peeled off
although 40°C or less.
Do not install in any location that is subject to large amounts of vibration.
Note: If the VF-FS1 Inverter is installed in a location that is subject
to vibration, anti-vibration measures are required. Please
consult with Toshiba about these measures.
If the VF-FS1 Inverter is installed near any of the equipment listed below, provide measures to insure
against errors in operation.
Solenoids: Attach surge suppressor on coil.
Brakes: Attach surge suppressor on coil.
Magnetic contactors: Attach surge suppressor on coil.
Fluorescent lights: Attach surge suppressor on coil.
Resistors: Place far away from VF-FS1 Inverter.
Resistors