6.8 Auto-stop in case of lower-limit frequency continuous
operation
6.8.1 Auto-stop in case of lower-limit frequency continuous
operation
H : Auto-stop in case of lower-limit frequency continuous operation
Function
If operation is carried out continuously at a frequency command below the lower-limit frequency (
NN) for
the period of time set with
H, the inverter will automatically slow down the motor to a stop. At that
time, “
NUVR” is displayed (alternately) on the operation panel.
This function will be canceled if a frequency command above the lower-limit frequency (
NN) +0.2Hz.
[Parameter setting]
Title Function Adjustment range Default setting
H
Auto-stop in case of lower-limit
frequency continuous operation time
0.0: Disabled
0.1-600.0 (s)
0.0
Note: This function is enabled even at the start of operation and during switching between forward and
reverse run.
Output frequency [Hz]
NN+0.2Hz
NN
Operation signal (F or R)
Time [s]
H
ON
OFF
HH