[Alarm information] Each message in the table is displayed to give a warning but does not cause the inverter to
trip.
Error code Problem Possible causes Remedies
QHH
ST terminal OFF
The ST-CC circuit is opened. Close the ST-CC circuit.
OQHH
Undervoltage in main
circuit
The supply voltage between R, S and T is
under voltage.
Measure the main circuit supply voltage.
If the voltage is at a normal level, the
inverter requires repairing.
TVT[
Retry in process
The inverter is n the process of retry.
A momentary stop occurred.
The inverter is normal if it restarts after
several tens of senconds.
The inverter restarts automatically. Be
careful of the machine because it may
suddenly restart.
GTT
Frequency point
setting error alarm
The frequency setting signals at points 1
and 2 are set too close to each other.
Set the frequency setting signals at points
1 and 2 apart from each other.
ENT
Clear command
acceptable
This message is displayed when pressing
the STOP key while an error code is
displayed.
Press the STOP key again to clear the
trip.
GQHH
Emergency stop
command
acceptable
The operation panel is used to stop the
operation in automatic control or remote
control mode.
Press the STOP key for an emergency
stop.
To cancel the emergency stop, press any
other key.
J/
NQ
Setting error alarm /
An error code and
data are displayed
alternately twice
each.
An error is found in a setting when data is
reading or writing.
Check whether the setting is made
correctly.
JGCF/
GPF
Display of first/last
data items
The first and last data item in the CWJ
data group is displayed.
Press MODE key to exit the data group.
FD
DC braking
DC braking in process The message goes off in several tens of
seconds if no problem occurs. Note)
FDZP
Shaft fixing control
Motor shaft fixing control is in process. Normal if the message disappears when
a stop command is entered (or the
operation command is canceled).
G
Flowing out of
excess number of
digits
The number of digits such as frequencies
is more than 4.
(The upper digits have a priority.)
Lower the fequency free unit
magnification H.
UVQR
Instantaneous power
failure coast stop
function activated.
The coast stop function set with H
(Instantaneous power failure coast stop)
is activated.
To restart operation, reset the inverter or
input an operation signal again.
NUVR
Auto-stop because of
continuous operation
at the lower-limit
frequency
The automatic stop function selected with
H was activated.
To deactivate the automatic stop function,
increase the frequency command above
the lower-limit frequency (LL) + 0.2 Hz or
turn off the operation command.
KPKV
Parameters in the
process of
initialization
Parameters are being initialized to default
values.
Normal if the message disappears after a
while (several seconds to several tens of
seconds).
G
Operation panel key
fault
The RUN or STOP key is held down for
more than 20 seconds.
The RUN or STOP key is faulty.
Check the operation panel.
CVP
Auto-tuning
Auto-tuning in process Normal if it the message disappears after
a few seconds.
M
Integral input power
Integral input power is more than
999.99kWh.
Press and hold down the ENT key for 3
seconds or more when power is off or
when the input terminal function CKWH
is turned on or displayed.
J
Integral output power
Integral output power is more than
999.99kWh.
Press and hold down the ENT key for 3
seconds or more when power is off or
when the input terminal function CKWH
is turned on or displayed.
Note: When the ON/OFF function is selected for DC braking (DB), using the input terminal selection parameter,
you can judge the inverter to be normal if “FD” disappears when opening the circuit between the terminal and
CC.