E6581381
E-3
5
[Parameter setting]
Title Function Adjustment range Default setting
CEE Acceleration time 1 0.0-3200 sec.
According to model
(⇒ See page K-14)
FGE
Deceleration time 1 0.0-3200 sec.
According to model
(⇒ See page K-14)
Note:When the acceleration/deceleration time is set at 0.0 seconds, the inverter speed increases or reduces
speed within 0.05 seconds.
+ If the programmed value is shorter than the optimum acceleration/deceleration time determined by load
conditions, overcurrent stall or overvoltage stall function may make the acceleration/deceleration time
longer than the programmed time. If an even shorter acceleration/deceleration time is programmed, there
may be an overcurrent trip or overvoltage trip for inverter protection.
⇒ For further details, see section 13.1.