[Parameter setting]
Title Function Adjustment range Default setting
H
VIA input point 1 setting 0-100 (%) 0
H
VIA input point 1 frequency 0.0-200.0 (Hz) 0.0
H
VIA input point 2 setting 0-100 (%) 100
H
VIA input point 2 frequency 0.0-200.0 (Hz)
50.0 (WP type)
60.0 (WN type)
H
VIB input point 1 setting 0-100 (%) 0
H
VIB input point 1 frequency 0.0-200.0 (Hz) 0.0
H
VIB input point 2 setting 0-100 (%) 100
H
VIB input point 2 frequency 0.0-200.0 (Hz)
50.0 (WP type)
60.0 (WN type)
H
Communication command point 1 setting 0-100 (%) 0
H
Communication command point 1 frequency 0.0-200.0 (Hz) 0.0
H
Communication command point 2 setting 0-100 (%) 100
H
Communication command point 2 frequency 0.0-200.0 (Hz)
50.0 (WP type)
60.0 (WN type)
Note: Don't set the same value between point 1 and point 2. If set the same falue, the GTT is displayed.
1) 0-10Vdc voltage input adjustment (VIA, VIB)
V
IA, VIB terminals
The output frequenc
y
with
respect to the voltage input is
adjusted according to the
selected reference point.
Gradient and bias can be set
easily.
H H
100 (%)
10V voltage signal
H H
0 ( Hz)
H H
0 (%)
H H
60 ( Hz )
0
Output
frequency
Frequenc
y
commnd
2) 4-20mAdc current input adjustment (VIA: VIA (SW3) slide switch in the I position)
V
IA terminal
The output frequency with respect to
the current input is adjusted
according to the selected reference
point.
Gradient and bias can be set easily.
Set
H
to
to create a current
input from 0 to 20mA.
H
100 (%)
20mA current signal
H
0 ( Hz)
H
20 (%)
4
H
60 ( Hz )
Output
frequency
Frequency commnd