Toshiba VF-FS1 Power Supply User Manual


 
E6581381
J-1
10
10. Peripheral devices
Danger
Mandatory
When using switchgear for the inverter, it must be installed in a cabinet.
Failure to do so can lead to risk of electric shock and can result in death or serious injury.
Be Grounded
Connect earth cables securely.
Failure to do so can lead to risk of electric shock or fire in case of a failure or short-circuit or electric
leak.
10.1 Selection of wiring materials and devices
Wire size (See Note 4)
Power circuit
(mm
2
) Note 1)
Earth cable
(mm
2
)
Voltage
class
Capacity of
applicable motor
(kW)
Inverter model
For IEC60364-5-
523/54
For JAPAN
JEAC8001-1995
For IEC60364-5-
523/54
For JAPAN
JEAC8001-1995
0.4 VFFS1-2004PM 1.5 2 2.5 2
0.75 VFFS1-2007PM 1.5 2 2.5 2
1.5 VFFS1-2015PM 1.5 2 2.5 2
2.2 VFFS1-2022PM 1.5 2 2.5 2
4.0 VFFS1-2037PM 2.5 2 2.5 2
5.5 VFFS1-2055PM 4 3.5 4 3.5
7.5 VFFS1-2075PM 6 5.5 6 3.5
11 VFFS1-2110PM 10 14 10 5.5
15 VFFS1-2150PM 16 14 16 5.5
18.5 VFFS1-2185PM 25 22 16 8
22 VFFS1-2220PM 25 38 16 8
Three-phase
200V class
30 VFFS1-2300PM 50 38 25 14
0.4 VFFS1-4004PL 1.5 2 2.5 2
0.75 VFFS1-4007PL 1.5 2 2.5 2
1.5 VFFS1-4015PL 1.5 2 2.5 2
2.2 VFFS1-4022PL 1.5 2 2.5 2
4.0 VFFS1-4037PL 1.5 2 2.5 2
5.5 VFFS1-4055PL 1.5 2 2.5 2
7.5 VFFS1-4075PL 1.5 2 2.5 2
11 VFFS1-4110PL 4 3.5 4 3.5
15 VFFS1-4150PL 6 5.5 6 3.5
18.5 VFFS1-4185PL 6 5.5 6 5.5
22 VFFS1-4220PL 10 8 10 5.5
Three-phase
400V class
30 VFFS1-4300PL 16 14 16 5.5
Note 1: Sizes of the wires connected to the input terminals R/L1, S/L2 and T/L3 and the output terminals U/T1,
V/T2 and W/T3 when the length of each wire does not exceed 30m.
Note 2: For the control circuit, use shielded wires 0.75 mm
2
or more in diameter.
Note 3: For grounding, use a cable with a size equal to or larger than the above.
Note 4: The wire sizes specified in the above table apply to HIV wires (cupper wires shielded with an insulator
with a maximum allowable temperature of 75°C) used at an ambient temperature of 40°C or less.
Note 5: If there is a need to bring the inverter into UL compliance, use wires specified in Chapter 9.