2) Preset-speed frequency setting
Set the speed (frequency) of the number of steps necessary.
Title Funtion Adjustment range Default setting
UT Preset-speed operation frequencies 1 NN WN(Hz) 15.0
UT Preset-speed operation frequencies 2 NN WN(Hz) 20.0
UT Preset-speed operation frequencies 3 NN WN(Hz) 25.0
UT Preset-speed operation frequencies 4 NN WN(Hz) 30.0
UT Preset-speed operation frequencies 5 NN WN(Hz) 35.0
UT Preset-speed operation frequencies 6 NN WN(Hz) 40.0
UT Preset-speed operation frequencies 7 NN WN(Hz) 45.0
Examples of preset-speed contact input signals: Slide switch SW4 set to sink logic
O: ON -: OFF (Speed commands other than preset-speed commands are valid when all are OFF)
Preset-speed
Terminal
1234567
R-CC
{
-
{
-
{
-
{
RES-CC -
{{
--
{{
VIA-CC - - -
{{{{
+ Preset-speed commands are not allocated to standard default setting. Use the input terminal function
selection to allocate SS1 to SS3 terminal.
Terminal R...............Input terminal function selection 2 (R)
H= (Preset-speed command 1: SS1)
Terminal RES..........Input terminal function selection 3 (RES)
H= (Preset-speed command 2: SS2)
Terminal VIA...........Input terminal function selection 8 (VIA)
H= (Preset-speed command 3: SS3)
Analog/contact input function selection
H= (VIA-contact input(Sink))
[Example of a connection diagram]
(SW4 set to sink logic)
F (Forward run)
CC
P24
RES
VIA
R
Forward
Preset-speed 1 (SS1)
Preset-speed 3 (SS3)
Preset-speed 2 (SS2)
Common
VIA
V
I
SW3
CC
R
RES
VIA