5.4 Meter setting and adjustment
HOUN : Meter selection
HO
: Meter adjustment
Function
The signal output from the FM terminal is an analog voltage signal.
For the meter, use either a full-scale 0-1mAdc ammeter or full-scale 0-7.5Vdc (or 10Vdc-1mA) voltmeter.
Switching to 0-20mAdc (4-20mAdc) output current can be made by turning the FM (SW2) slide switch to
the I position. When switching to 4-20mAdc current input, make adjustments using H (analog
output gradient) and H (analog output bias).
[Parameter setting]
Title Function Adjustment range
Supposition output at
HOUN=
Default setting
0:Output frequency Maximum frequency (HJ)
1:Output current 1.5 times of rated current
2:Set frequency Maximum frequency (HJ)
3:DC voltage 1.5 times of rated voltage
4:Output voltage command value 1.5 times of rated voltage
5:Input power 1.85 times of rated power
6:Output power 1.85 times of rated power
7:Torque 2.5 times of rated torque
8:Torque current 2.5 times of rated torque
9:Motor cumulative load factor Rated load factor
10: Inverter cumulative load factor
11: - (Do not select)
Rated load factor
-
12: Frequency setting value (after PID) Maximum frequency (HJ)
13: VIA Input value Maximum input value
14: VIB Input value Maximum input value
15: Fixed output 1 (Output current: 100%) -
16: Fixed output 2 (Output current: 50%) -
17: Fixed output 3
(Supposition output at HOUN=17)
-
18: Serial communication data FA51=1000
HOUN
Meter
selection
19: For adjustments (HOset value is
displayed.)
-
0
HO
Meter
adjustment
---