E6581381
B-7
2
Terminal
symbol
Input/output Function
Electrical
specifications
Inverter internal circuits
PP Output Analog power supply output
10Vdc
(permissible load
current: 10mA)
VIA Input
Multifunction programmable analog input.
Factory default setting: 0~10Vdc/0~60Hz
(0~50Hz) frequency input.
The function can be changed to
4~20mAdc (0~20mA) current input by
flipping the VIA (SW3) dip switch to the I
position.
By changing parameter setting, this
terminal can also be used as a
multifunction programmable contact input
terminal. When using the sink logic, be
sure to insert a resistor between P24-VIA
(4.7 k
Ω-1/2 W). Also move the VIA (SW3)
dip switch to the V position.
10Vdc
(internal impedance:
30k
Ω)
4-20mA
(internal impedance:
250
Ω)
VIB Input
Multifunction programmable analog input.
Standard default setting: 0~10Vdc/0~60Hz
(0~50Hz) frequency input.
PTC thermal input
⇒ See section 6.17.15.
10Vdc
(internal
impedance: 30k
Ω)
FM Output
Multifunction programmable analog
output. Standard default setting: output
frequency.
The function can be changed to 0-20mAdc
(4-20mA) current output by flipping the FM
(SW2) slide switch to the I position.
1mAdc full-scale
ammeter or 7.5Vdc
(10Vdc)1mA full-
scale voltmeter
0-20mA (4-20mA)
DC ammeter
Permissible load
resistance:
750
Ω or less
P24 Output 24Vdc power output 24Vdc-50mA
* PTC (Positive Temperature Coefficient) : Resettable thermal fuse resistor for over current protection
*