Error code Failure code Problem Possible causes Remedies
QR
000A Overvoltage during
acceleration
The imput voltage fluctuates abnormally.
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
(3) A system using a thyrister is connected
to the same power distribution line.
A restart signal is input to the rotating
motor after a momentary stop, etc.
There is possibility of output phase
failure.
Insert a suitable input reactor.
Use H (auto-restart) and H
(coast stop).
Check the main circuit output line, motor,
etc. for phase failure.
QR
000B Overvoltage during
deceleration
The deceleration time FGE is too short.
(Regenerative energy is too large.)
H (overvoltage limit operation) is
off.
The input voltage fluctuates abnormally.
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened and closed.
(3) A system using a thyrister is connected
to the same power distribution line.
There is possibility of output phase
failure.
Increase the deceleration time FGE.
Enable H (overvoltage limit
operation).
Insert a suitable input reactor.
Check the main circuit output line, motor,
etc. for phase failure.
QR
000C Overvoltage during
constant-speed
operation
The input voltage fluctuates abnormally.
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
(3) A system using a thyrister is connected
to the same power distribution line.
The motor is in a regenerative state
because the load causes the motor to run
at a frequency higher than the inverter
output frequency.
There is possibility of output phase
failure.
Insert a suitable input reactor.
Check the main circuit output line, motor,
etc. for phase failure.
QN
000D Inverter overload
The acceleration time ACC is too short.
The DC braking amout is too large.
The V/F setting is improper.
A restart signal is input to the rotating
motor after a momentary stop, etc.
The load is too large.
Increase the acceleration time CEE.
Reduce the DC braking amount H
and the DC braking time H.
Check the V/F parameter setting.
Use H (auto-restart) and H
(coast stop).
Use an inverter with a larger rating.
QN
000E Motor overload
The V/F setting is improper.
The motor is locked up.
Low-speed operation is performed
continuously.
An excessive load is applied to the motor
during operation.
Check the V/F parameter setting.
Check the load (operated machine).
Adjust QNO to the overload that the
motor can withstand during operation in a
low speed range.
*
QV
0020 Over-torque trip
Over-torque reaches to a detection level
during operation.
Enable H (over-torque trip
selection).
Check system error.
QJ
0010 Overheat
The cooling fan does not rotate.
The ambient temperature is too high.
The vent is blocked up.
A heat generating device is installed close
to the inverter.
The thermistor in the unit is broken.
Restart the operation by resetting the
inverter after it has cooled down enough.
The fan requires replacement if it does
not rotate during operation.
Secure sufficient space around the inverter.
Do not place any heat generating device
near the inverter.
Make a service call.