ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance
2-181
© 2000, ADC Telecommunications, Inc.
DLP-556
Page 2 of 3
6. Move to the
Mon Type Alarms
toggle fields. The following selections are possible:
• Critical Allows notification of all Critical, Major, Minor, and Event alarms as they
occur.
• Major Allows notification of all Major, Minor, and Event alarms as they occur.
• Minor Allows notification of all Minor and Event alarms as they occur.
• Event Allows notification of all events as they occur.
Reference
: TAP-101 Alarm Troubleshooting
7. Assign the selections by pressing Enter or Return.
8. Repeat Steps 3 through 7 for each applicable DS1 signal in the chassis.
Note:
Pressing CONTROL-C and confirming with the Y key removes all threshold
values and alarm level information from the database for the group and slot selected.
Stop! You have completed this procedure.
6146-B
DS1 PERFORMANCE MONITORING CONFIGURATION
Group: 1 Circuit: 1 Circuit ID:
15 MINUTE DAILY 15 MINUTE DAILY
MON ============== ================ MON ============== ================
TYPE THRSH ALM LVL THRSH ALM LVL TYPE THRSH ALM LVL THRSH ALM LVL
==== ===== ======== ======= ======== ======== ===== ======== ======= ========
FCP 5 EVENT 480 EVENT AISSP 10 EVENT 100 EVENT
CVL 13340 EVENT 133400 EVENT FCP-FE 5 EVENT 480 EVENT
ESL 65 EVENT 648 EVENT ESL-FE 65 EVENT 648 EVENT
SESL 10 EVENT 100 EVENT CVP-FE 13340 EVENT 133400 EVENT
LOSS 10 EVENT 100 EVENT ESP-FE 65 EVENT 648 EVENT
CVP 13340 EVENT 133400 EVENT SESP-FE 10 EVENT 100 EVENT
ESP 65 EVENT 648 EVENT UASP-FE 10 EVENT 100 EVENT
SESP 10 EVENT 100 EVENT CSSP-FE 10 EVENT 100 EVENT
UASP 10 EVENT 100 EVENT SEFSP-FE 10 EVENT 100 EVENT
SASP 10 EVENT 100 EVENT
CVs PER SESL: 1544 CVs PER SESP: 330 CVs PER SESP-FE: 330
Press CONTROL-A For Assistance, CONTROL-C To Clear All PM Counts
* Indicates valid range of values for selected field. See Table 556-1.
Figure 556-1. DS1 PM Configuration Screen