ADC Broadband System Network Router User Manual


 
ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance
2-197
© 2000, ADC Telecommunications, Inc.
DLP-562
Page 2 of 3
8. Move to the
HDSL Facility Alarms
toggle fields. Select
CRITICAL, MAJOR, MINOR,
EVENT, or NOT RPTD for each field that you wish to change.
Reference
: TAP-101 Alarm Troubleshooting
9. Assign the selections by pressing Enter or Return.
Stop! You have completed this procedure.
6153-C
HLX ALARM LEVELS
Group: 6 Slot: 1
Equipment Alarms
=============================================================================
COMM FAIL : MAJOR HSKP1 : MINOR PRIMARY POWER : MAJOR
LOOP REVERSAL : EVENT HSKP2 : MINOR SECONDARY POWER : MAJOR
TP/RNG REVERSAL : EVENT VERSION MISMATCH: MAJOR
DS1 Facility Alarms
=============================================================================
AIS : EVENT LOF : MAJOR T-BERL : MINOR
CUSTOMER LOOPBACK: MINOR LOS : MAJOR YELLOW : EVENT
NETWORK LOOPBACK : MINOR
HDSL Facility Alarms
=============================================================================
DC CONTINUITY : MAJOR T-BERP FE: MINOR T-SNR FE : EVENT
LOF FE : MAJOR T-BERP NE: MINOR T-SNR NE : EVENT
LOF NE : MAJOR T-PA FE : EVENT
RECOVERY : MINOR T-PA NE : EVENT
Press CONTROL-A For Assistance
Figure 562-1. HLX Alarm Levels Screen (with Default Values)