ADC Broadband System Network Router User Manual


 
ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance
2-47
© 2000, ADC Telecommunications, Inc.
DLP-510
Page 2 of 2
9. At the chassis location, insert a test signal into the DS1 to be tested using the DS3 test set
with DS1 option.
10. Verify that all alarm indicators on the chassis are off and the DS1 test set at the QFLC or
QLX DS1 output is receiving error-free data for the DS1 test signal selected.
11. Repeat Steps 9 and 10 for all DS1 circuits to be tested on the ODS2 module selected.
12. At the QFLC or QLX location, insert a DS1 test signal into the QFLC or QLX DS1 input
using the DS1 test set.
13. Verify that all alarm indicators on the chassis are out and the DS3 test set with DS1 option
is receiving error-free data in the DS1 selected for test.
14. Repeat Steps 12 and 13 for all DS1 circuits to be tested on the ODS2 module selected.
15. Repeat procedure starting at Step 3 for all ODS2 modules to be tested.
16. Record test results and update office records following local office practices.
Stop! You have completed this procedure.