ADCP-61-471 • Issue 4 • June 2000 • Section 2: Operation and Maintenance
2-200
© 2000, ADC Telecommunications, Inc.
DLP-563
Page 2 of 2
7. Move to the
DS1 Facility Alarms
toggle fields. Select
CRITICAL, MAJOR, MINOR,
EVENT, or NOT RPTD for each field that you wish to change.
Reference
: TAP-101 Alarm Troubleshooting
8. Assign the selections by pressing Enter or Return.
Stop! You have completed this procedure.
6154-B
DLX ALARM LEVELS
Group: 5 Slot: 1
Equipment Alarms
==========================
COMM FAIL : MAJOR
DS1 Facility Alarms
==========================
CUSTOMER LOOPBACK: MINOR
LOS : MAJOR
T-BERL : MINOR
Press CONTROL-A For Assistance
NETWORK LOOPBACK : MINOR
Figure 563-1. DLX Alarm Level Defaults