Select Configuration Protection
This feature can be used to protect the remote drop configuration, preventing changes
from the CPU or Hand–held Monitor. It can only be selected from a Hand–held
Monitor. To make subsequent changes, protection must be removed again using a
Hand–held Monitor. Before the remote drop is used, its configuration should be
protected.
After a Remote I/O Scanner has been configured from Logicmaster 90–70, its
configuration is automatically protected. If you want to use a Hand–held Monitor to
change a Logicmaster 90–70 configuration, you must first disable configuration
protection on this screen. Logicmaster 90–70 can always configure a remote drop,
regardless of of its configuration protect state.
HHM Display
CONFIG PROTECT
DISABLED
tgl entr nxt
Configuration Steps
1. If the selection shown on line 3 should be changed, press F2 (tgl). Press F3 (entr).
2. This is the last configuration screen.
Finishing Configuration
That completes HHM configuration of the remote drop. The configuration is stored by
the Remote I/O Scanner, and will survive loss of power.
If the baud rate was changed, and the remote drop is on an operating bus, cycle power
to all devices on the bus at the same time to use the new baud rate.