Display and Clear Faults from Logicmaster 90–70
The content of the PLC and I/O Fault Table displays depends on whether the
programmer is communicating with the PLC or a remote drop.
I/O Fault Table at the PLC
The content of the fault display at the PLC depends on the revision level of the Bus
Controller. With a Bus Controller that is version 4.0 or later, when a fault occurs on a
remote drop, the I/O Fault Table shows the Drop ID and the rack and slot within the
remote drop where the fault has occurred:
33#0.4
Drop ID
Rack
Slot
Remote Drop Fault
Drop ID#, rack, slot
Genius Bus Fault
rack, slot, bus,
bus address
|PROGRM |TABLES |STATUS | | |LIB |SETUP |FOLDER |UTILTY |PRINT
1plcrun 2passwd 3plcflt 4io flt 5plcmem 6blkmem 7refsiz 8sweep 9clear 10zoom
>
I / O F A U L T T A B L E
TOP FAULT DISPLAYED: 0001 TABLE LAST CLEARED: 09–21 08:00:00
TOTAL FAULTS: 0007 ENTRIES OVERFLOWED: 0000
FAULT DESCRIPTION: OPEN WIRE PLC DATE/TIME: 10–14 10:05:13
FAULT CIRC REFERENCE FAULT FAULT DATE TIME
LOCATION NO. ADDR. CATEGORY TYPE M–D H: M: S
___________ _____ _________ ___________________ ________________ _____ ________
33#0.4 6 %AI0101 CIRCUIT FAULT ANALOG FAULT 10–12 08:12:20
0.3.1.5 %Q01009 ADD’N OF DEVICE 10–12 08:12:22
MAINPLC RUN/ENABLE 7MS SCAN ONLINE L4 ACC: WRITE CONFIG CONFIG EQUAL
PLC C: LESSON PRG: LESSON
REPLACE
I/O Fault Table Display with a Rev. 3 Bus Controller
If the Bus Controller is a rev. 3 version, it cannot transfer to the PLC the detailed fault
information provided by a Remote I/O Scanner. Instead, a rev. 3 Bus Controller reports
any fault from a remote drop as a GENA fault.
Fault Clearing
To clear the fault table, press the Clear key.