121Chapter 8 Diagnostics and Fault Clearing
Display and Clear Faults from Logicmaster 5 or Logicmaster 6
If the host CPU is a Series Five or Series Six PLC, faults from a remote drop are
displayed in the Genius Fault Table. A Logicmaster 6 fault table is illustrated below.
The Logicmaster 5 fault table is similar.
Faults from remote drops are identified as GENA faults. The GENA is the component
within the Remote I/O Scanner that handles the Genius bus interface.
L/M: OFFLINE
TOTAL FAULTS: 0000 GENIUS I/O FAULT TABLE date
TOP FAULT DISPLAYED:0000 time
FAULT DISPLAYED: 0000:00:00:00:0
B/C POINT CIRC FAULT FAULT FAULT
ADDR. ADDR. NO. CATEGORY TYPE DESCRIPTION DAY:HR:MN:SC:T
––––– –––––– –––– –––––––––––––––– –––––––– ––––––––––––––– –––––––––––––––
0 0 I0001 1 CIRCUIT FAULT DISCRETE OPEN WIRE 147:12:03:12:44
0 64 O0053 6 CIRCUIT FAULT DISCRETE NO LOAD 147:13:56:31:04
1 32 IO001 GENA 148:03:12:48:55
NEXT PREV CLEAR XPNDED
1 PAGE 2 PAGE 3FAULTS 4 TOP 5BOTTOM 6 7 8 FUNC
Fault Clearing
Pressing the Clear Faults key clears all faults currently in the fault table. This sets the
fault count to zero, and sends a Clear command to the Remote I/O Scanner.