69Chapter 4 Configuration with Logicmaster 90–70
Reference Overlaps
If you have entered a conflicting reference address, the following warning appears:
Overlapping addresses
Overlapping references are permitted in %Q and %AQ. Overlapping references in %I
and %AI are not permitted; such a configuration is not valid.
With the next press of any key after the message appears, the configuration is saved to
disk. Return to the Remote Drop configuration screens and remove the conflict.
In the example illustrated above, the duplicated references appear on the same screen,
so they are easy to locate and correct. If you are not sure where the conflicting
references are located, use the Reference View feature. See page 71 for more
information about Reference View.