Schneider Electric IP67 Computer Hardware User Manual


 
The Object Dictionary
136
1606218 02 08/2006
Object 1001H: Error Register
Description This object is used by the device to display internal faults. When a fault is detected,
the corresponding bit is therefore activated.
The following faults can be displayed:
Characteristics The characteristics of this object are given in the following FTB splitter box table:
Bit Meaning Comments
0 Generic error -
1 Current fault (overload or short-
circuit)
-
2 Voltage fault -
3 Temperature Unchecked
4 Communication error -
5 Reserved Unchecked
6 Reserved Unchecked
7 Specific to the manufacturer Detection of wire cut
Sub-index Description Data type Default value Access PDO Mapping Backed up
- - UNSIGNED8 - ro no no