List of
FTB 1CN16CP0
and
FTB 1CN16CM0
Output Objects
The list of output objects for the Advantys FTB 1CN16CP0 and FTB 1CN16CM0
splitter boxes is given in the following table:
6102H 1 Bit 0 Channel 0 polarity if channel 0 configured for input
Not assigned if channel 0 configured for output
... ...
Bit 15
Channel 17 polarity if channel 17 configured for input
Not assigned if channel 17 configured for output
6103H 1 Bit 0
Channel 0 masking if channel 0 configured for input
Not assigned if channel 0 configured for output
... ...
Bit 15
Channel 17 masking if channel 17 configured for input
Not assigned if channel 17 configured for output
Note: All the objects are 16-bit word tables except for 2000H and 6000H.
Sub-index 1 of object 6000H corresponds to the 6100H (pin 4) object's least
significant byte
Object 2000H, read by byte, concerns channels 10 to 17 only (pin 2).
Object Sub-
index
Bit Description
Object Sub-
index
Bit Description
6200H 1 Bit 0
Channel 0 output writing if channel 0 configured for output
Not assigned if channel 0 configured for input
... ...
Bit 7
Channel 7 output writing if channel 7 configured for output
Not assigned if channel 7 configured for input
2Bit 0
Channel 10 output writing if channel 10 configured for output
Not assigned if channel 10 configured for input
... ...
Bit 7
Channel 17 output writing if channel 17 configured for output
Not assigned if channel 17 configured for input
6300H 1 Bit 0
Channel 0 output writing if channel 0 configured for output
Not assigned if channel 0 configured for input
... ...
Bit 15
Channel 17 output writing if channel 17 configured for output
Not assigned if channel 17 configured for input