Schneider Electric IP67 Computer Hardware User Manual


 
Application-Specific Functions
1606218 02 08/2006 85
List of Advantys FTB 1CN16EP0 and FTB 1CN16EM0 Splitter Box I/O Objects
List of
FTB 1CN16EP0
and
FTB 1CN16EM0
Input Objects
The list of input objects for the Advantys FTB 1CN16EP0 and FTB 1CN16EM0
splitter boxes is given in the following table:
Object Sub-
index
Bit Description
2000H 1 Bit 0 Choice between the "input" function and the "diagnostics input"
function for channel 10
... ...
Bit 7 Choice between the "input" function and the "diagnostics input"
function for channel 17
6000H 1 Bit 0 Reading of channel 0 input
... ...
Bit 7 Reading of channel 7 input
2 Bit 0 Reading of channel 10 input
... ...
Bit 7 Reading of channel 17 input
6100H 1 Bit 0 Reading of channel 0 input
... ...
Bit 15 Reading of channel 17 input
6102H 1 Bit 0 Polarity of channel 0
... ...
Bit 15 Polarity of channel 17
6103H 1 Bit 0 Channel 0 masking
... ...
Bit 15 Channel 17 masking
Note: All the objects are 16-bit word tables except for 2000H and 6000H.
Sub-index 1 of object 6000H corresponds to the 6100H (pin 4) object's least
significant byte
Sub-index 2 of object 6000H corresponds to the 6300H (pin 2) object's most
significant byte.
Object 2000H, read by byte, concerns channels 10 to 17 only (pin 2).