Schneider Electric IP67 Computer Hardware User Manual


 
The Object Dictionary
1606218 02 08/2006 181
Object 6300H: Write Outputs 16 Bits
Description This object is used to command the state of discrete outputs.
Characteristics The characteristics of this object are outlined in the following table:
Note: The bits corresponding to a configured input channel are ignored.
Sub-index Description Data type Default value Access PDO
Mapping
Backed up
0 Sub-index number UNSIGNED8 1 ro no yes
1 Write outputs 16 bits UNSIGNED16 0 rw yes yes
RISK OF UNINTENDED EQUIPMENT OPERATION
It is not advisable to use the 6200H and 6300H objects simultaneously.
Where both these objects are used, the Advantys FTB splitter box executes the
most recent command received.
Failure to follow this instruction can result in death, serious injury, or
equipment damage.
WARNING