Schneider Electric IP67 Computer Hardware User Manual


 
Application-Specific Functions
1606218 02 08/2006 95
6307H 1 Bit 0 Channel 0 output fallback value if channel 0 configured for
output
Not assigned if channel 0 configured for input
... ...
Bit 7
Channel 7 output fallback value if channel 7 configured for
output
Not assigned if channel 7 configured for input
Bit 8 Not assigned
... ...
Bit 15 Not assigned
6308H 1 Bit 0
Channel 0 output masking if channel 0 configured for output
Not assigned if channel 0 configured for input
... ...
Bit 7
Channel 7 output masking if channel 7 configured for output
Not assigned if channel 7 configured for input
Bit 8 Not assigned
... ...
Bit 15 Not assigned
Note: All the objects are 16-bit word tables except for 6200H.
For object 6200H:
Sub-index 1 corresponds to the 6300H (pin 4) object's least significant byte
Sub-index 2 corresponds to the 6300H (pin 2) object's most significant byte
Object Sub-
index
Bit Description