Schneider Electric IP67 Computer Hardware User Manual


 
The Object Dictionary
1606218 02 08/2006 147
Back-up
Behavior
Writing a valid value
The device stores the parameters, and then confirms SDO transmission
(downloading initialization response).
Writing an invalid value
The device refuses storage and replies with an "Abort SDO Transfer" (Abort
Code:0800 002xH with x=0...F).
Storage Function During read access to an appropriate sub-index, the splitter box transmits
information on its storage function, in the following format:
Note: When storage fails, the splitter box returns an Abort SDO Transfer (Abort
Code:0606 0000H).
RISK OF UNINTENDED EQUIPMENT OPERATION
The splitter box must be switched to the "Pre-Operational" state to save its
configuration. The saving process takes 1 to 2 seconds. If the save takes place in
the "Operational" state, the outputs will not be updated during the saving process.
Failure to follow this instruction can result in death, serious injury, or
equipment damage.
WARNING
Bit 32 to 2 1 0
Meaning if bit
= 0
Reserved The splitter box does not store
parameters autonomously
The splitter box does not store
parameters when it receives a
command
Meaning if bit
= 1
Reserved The splitter box stores
parameters autonomously
The splitter box stores
parameters when it receives a
command