List of
FTB 1CN16CP0
and
FTB 1CN16CM0
Input Objects
The list of input objects for the Advantys FTB 1CN16CP0 and FTB 1CN16CM0
splitter boxes is given in the following table:
Object Sub-
index
Bit Description
2000H 1 Bit 0 Choice between the "input" function and the "diagnostics input"
function for channel 10
... ...
Bit 7 Choice between the "input" function and the "diagnostics input"
function for channel 17
6000H 1 Bit 0
Channel 0 input reading if channel 0 configured for input
Not assigned if channel 0 configured for output
... ...
Bit 7
Channel 7 input reading if channel 7 configured for input
Not assigned if channel 7 configured for output
2Bit 0
Channel 10 input reading if channel 10 configured for input
Channel 10 diagnostics input reading if channel 10 configured
for diagnostics input
Not assigned if channel 10 configured for output
... ...
Bit 7
Channel 17 input reading if channel 17 configured for input
Channel 17 diagnostics input reading if channel 17 configured
for diagnostics input
Not assigned if channel 17 configured for output
6100H 1 Bit 0
Channel 0 input reading if channel 0 configured for input
Not assigned if channel 0 configured for output
... ...
Bit 7
Channel 7 input reading if channel 7 configured for input
Not assigned if channel 7 configured for output
Bit 8
Channel 10 input reading if channel 10 configured for input
Channel 10 diagnostics input reading if channel 10 configured
for diagnostics input
Not assigned if channel 10 configured for output
... ...
Bit 15
Channel 17 input reading if channel 17 configured for input
Channel 17 diagnostics input reading if channel 17 configured
for diagnostics input
Not assigned if channel 17 configured for output