Schneider Electric IP67 Computer Hardware User Manual


 
Installation
22
1606218 02 08/2006
Method for
Plastic Units
Follow the steps below to connect the ground to the unit:
Position of the
Ground
Electrode on the
Metal Unit
The following figure shows the position of the ground electrode on the metal boxes.
Method for Metal
Units
Follow the steps below to connect the unit to the ground electrode:
Mounting the
Metal Unit
Once these steps have all been completed (see table above), the product can be
mounted on its support.
Step Action
1 Remove the label located above the symbol representing the ground.
2 Insert the end of the grounding strip into the grounding terminal of the splitter
box.
3 Screw in the ground connection screw.
Note: Use a grounding strip or a conductor with a cross-section of 1 to 1.5 mm
2
(AWG18, AWG16) and a length of 3 m (9.84 ft) long. The maximum
recommended length for the grounding strip is 3 m (9.84 ft).
Step Action
1 Crimp the lug on the ground cable.
2 Screw in the lug with the ground conductor connection screw (supplied with the
product).