Schneider Electric IP67 Computer Hardware User Manual


 
Application-Specific Functions
1606218 02 08/2006 93
6102H 1 Bit 0 Channel 0 input polarity if channel 0 configured for input
Not assigned if channel 0 configured for output
... ...
Bit 7
Channel 7 input polarity if channel 7 configured for input
Not assigned if channel 7 configured for output
Bit 8
Channel 10 input polarity if channel 10 configured for input
Channel 10 diagnostics input polarity if channel 10 configured
for diagnostics input
... ...
Bit 15
Channel 17 input polarity if channel 17 configured for input
Channel 17 diagnostics input reading if channel 17 configured
for diagnostics input
6103H 1 Bit 0
Channel 0 input masking if channel 0 configured for input
Not assigned if channel 0 configured for output
... ...
Bit 7
Channel 7 input masking if channel 7 configured for input
Not assigned if channel 7 configured for output
Bit 8
Channel 10 input masking if channel 10 configured for input
Channel 10 diagnostics input masking if channel 10
configured for diagnostics input
... ...
Bit 15
Channel 17 input masking if channel 17 configured for input
Channel 17 diagnostics input masking if channel 17
configured for diagnostics input
Note: All the objects are 16-bit word tables except for 2000H and 6000H.
Sub-index 1 of object 6000H corresponds to the 6100H (pin 4) object's least
significant byte
Object 2000H, read by byte, concerns channels 10 to 17 only (pin 2).
Object Sub-
index
Bit Description