Delta Electronics VFD-VL Network Card User Manual


 
Chapter 4 Parameters|
Revision Nov. 2008, VLE1, SW V1.03 4-45
Settings Functions Descriptions
20 Warning Output
Active when the warning is detected.
21 Over-voltage Warning
Active when the over-voltage is detected.
22
Over-current Stall
Prevention Warning
Active when the over-current stall prevention is detected.
23
Over-voltage Stall
prevention Warning
Active when the over-voltage stall prevention is detected.
24
Operation Mode
Indication
Active when the operation command is controlled by external
terminal. (Pr.00-15
0)
25 Forward Command
Active when the operation direction is forward.
26 Reverse Command
Active when the operation direction is reverse.
27
Output when Current >=
Pr.02-33
Active when current is >= Pr.02-33.
28
Output when Current <
Pr.02-33
Active when current is < Pr.02-33.
29
Output when frequency
>= Pr.02-34
Active when frequency is >= Pr.02-34.
30
Output when Frequency
< Pr.02-34
Active when frequency is < Pr.02-34.
31-32 Reserved
33
Zero Speed (actual
output frequency)
Active when the actual output frequency is 0. (the drive should
be at RUN mode)
34
Zero Speed with Stop
(actual output frequency)
Active when the actual output frequency is 0 or Stop. (the
drive should be at RUN mode)
35 Fault output option 1
Active when Pr.06-22 is ON.
36 Fault output option 2
Active when Pr.06-23 is ON.
37 Fault output option 3
Active when Pr.06-24 is ON.
38 Fault output option 4
Active when Pr.06-25 is ON.
39 Reserved