Delta Electronics VFD-VL Network Card User Manual


 
Chapter 4 Parameters|
Revision Nov. 2008, VLE1, SW V1.03 4-71
06-22 Fault Output Option 1 Unit: 1
06-23 Fault Output Option 2 Unit: 1
06-24 Fault Output Option 3 Unit: 1
06-25 Fault Output Option 4 Unit: 1
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: 0
Settings 0 to 65535 sec (refer to bit table for fault code)
These parameters can be used with multi-function output (set Pr.02-11 to Pr.02-22 to 35-38)
for the specific requirement. When the fault occurs, the corresponding terminals will be
activated (It needs to convert binary value to decimal value to fill in Pr.06-22 to Pr.06-25).
Bit0 Bit1 Bit2 Bit3 Bit4 Bit5 Bit6
Fault code
current Volt. OL SYS FBK EXI CE
0: No fault
1: Over-current during acceleration
(ocA)
2: Over-current during deceleration
(ocd)
3: Over-current during constant speed
(ocn)
4: Ground fault (GFF)
5: IGBT short-circuit (occ)
6: Over-curent at stop (ocS)
7: Over-voltage during acceleration
(ovA)
8: Over-voltage during deceleration
(ovd)
9: Over-voltage during constant speed
(ovn)
10: Over-voltage at stop (ovS)
11: Low-voltage during acceleration
(LvA)
12: Low-voltage during deceleration
(Lvd)
13: Low-voltage during constant
speed (Lvn)
14: Low-voltage at stop (LvS)