Delta Electronics VFD-VL Network Card User Manual


 
Chapter 4 Parameters|
4-76 Revision Nov. 2008, VLE1, SW V1.03
07-05 Start-Point for DC Brake Unit: 0.01
Control
mode
VF VFPG SVC FOCPG
Factory Setting: 0.00
Settings 0.00 to 120.00Hz
This parameter determines the frequency when DC Brake will begin during deceleration. When
the setting is less than start frequency (Pr.01-09), start-point for DC brake will begin from the
min. frequency.
ON
OFF
01-09
07-05
Output frequenc
y
Run/Stop
Time
DC Brake Time
DC Brake Time
during Stopping
Start
frequency
Start-point for
DC brake
time during
stopping
07-03
07-04
07-06 DC Brake Proportional Gain Unit: 1
Control
mode
VF VFPG SVC
Factory Setting: 50
Settings 1 to 500Hz
It is used to set the output voltage gain when DC brake.
07-07 Dwell Time at Accel. Unit: 0.01
Control
mode
VF VFPG SVC FOCPG FOCPM
Factory Setting: 0.00
Settings 0.00 to 600.00 sec
07-08 Dwell Frequency at Accel. Unit: 0.01
Control
mode
VF VFPG SVC FOCPG FOCPM
Factory Setting: 0.00
Settings 0.00 to 120.00 Hz
07-09 Dwell Time at Decel. Unit: 0.01
Control
mode
VF VFPG SVC FOCPG FOCPM
Factory Setting: 0.00
Settings 0.00 to 600.00 sec
07-10 Dwell Frequency at Decel. Unit: 0.01
Control
mode
VF VFPG SVC FOCPG FOCPM
Factory Setting: 0.00
Settings 0.00 to 120.00 Hz
In the heavy load situation, Dwell can make stable output frequency temporarily.