Delta Electronics VFD-VL Network Card User Manual


 
Chapter 4 Parameters|
4-64 Revision Nov. 2008, VLE1, SW V1.03
It is used to set the accel./decel. time selection when stall prevention occurs at constant speed.
06-05 Over-torque Detection Selection (OT1)
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: 0
Settings 0 Over-Torque detection disabled.
1 Over-torque detection during constant speed operation, continue to
operate after detection
2 Over-torque detection during constant speed operation, stop
operation after detection
3 Over-torque detection during operation, continue to operate after
detection
4 Over-torque detection during operation, stop operation after
detection
06-06 Over-torque Detection Level (OT1) Unit: 1
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: 150
Settings 10 to 250%
06-07 Over-torque Detection Time (OT1) Unit: 0.1
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: 0.1
Settings 0.0 to 60.0 sec
06-08 Over-torque Detection Selection (OT2)
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: 0
Settings 0 Over-Torque detection disabled.
1 Over-torque detection during constant speed operation, continue to
operate after detection
2 Over-torque detection during constant speed operation, stop
operation after detection
3 Over-torque detection during operation, continue to operate after
detection
4 Over-torque detection during operation, stop operation after
detection
06-09 Over-torque Detection Level (OT2) Unit: 1
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: 150
Settings 10 to 250%