Delta Electronics VFD-VL Network Card User Manual


 
Chapter 4 Parameters|
Revision Nov. 2008, VLE1, SW V1.03 4-35
01-24
01-25
01-26
01-27
Frequency
Time
01-29 Switch Frequency for S3/S4 Changes to S5 Unit: 0.01
Control
mode
VF VFPG SVC FOCPG FOCPM
Factory setting: 0.00
Settings 0.00~120.00Hz
It is used to set the switch frequency between S4 and S5 for smooth stop.
It is recommended to set this parameter to the leveling speed of elevator.
Frequenc
y
01-12
accel. time
01-13
decel. time
Time
01-25=S2
01-26=S3
01-24=S1
01-27=S4
01-30=S5
01-29
Switch frequency
for S3/S4 changes
to S5
01-28
Mode Selection when Frequency< Fmin
Control
mode
VF VFPG SVC
Factory setting: 0
Settings 0 Output Waiting
1
Zero-speed operation
2
Fmin (4th output frequency setting)
When the AC motor drive is at 0Hz, it will operate by this parameter.
When it is set to 1 or 2, voltage will be output by Fmin corresponding output voltage.
01-31
Deceleration Time when Operating without RUN
Command
Unit: 0.01
Control
mode
VF VFPG SVC FOCPG FOCPM
Factory setting: 2.00
Settings 0.00~600.00 Sec