Delta Electronics VFD-VL Network Card User Manual


 
Chapter 4 Parameters|
Revision Nov. 2008, VLE1, SW V1.03 4-81
07-28
Emergency Stop (EF) & Forced Stop Selection
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory Setting: 0
Settings 0 Coast to stop
1 By deceleration Time 1
2 By deceleration Time 2
3 By deceleration Time 3
4 By deceleration Time 4
5 By Pr.01-31
When the multi-function input terminal is set to 10 or 14 and it is ON, the AC motor drive will be
operated by Pr.07-28.
07-29 Time for Decreasing Torque at Stop Unit: 0.001
Control
mode
FOCPG TQCPG FOCPM
Factory Setting: 0.000
Settings 0.000 to 1.000 sec
It is used to set the time for decreasing torque to 0%.
RUN/STOP
0%
i
t
i
00-01
x
100%
300%
x
(07-29)=t