Delta Electronics VFD-VL Network Card User Manual


 
Chapter 4 Parameters|
Revision Nov. 2008, VLE1, SW V1.03 4-17
Group 11 Advanced Parameters
Pr. Explanation Settings
Factory
Setting
VF
VFPG
SVC
FOCPG
TQCPG
FOCPM
11-00
System Control
Bit 0=0: no function
Bit 0=1: ASR Auto tuning, PDFF enable
Bit 7=0: no function
Bit 7=1: When position control is enabled, it doesn’t need to set
Pr.07-02 (DC Brake Current Level)
Bit 15=0: when power is applied, it will detect the position of
magnetic field again
Bit 15=1: when power is applied, it will start from the magnetic
field position of previous power failure
0
11-01
Elevator Speed
0.10~3.00 m/s 1.00
11-02
Sheave Diameter
100~2000 mm 400
11-03
Mechanical Gear Ratio
1~100 1
11-04
Suspension Ratio
0: 1:1
1: 2:1
1
11-05
Inertial Ratio
1~300% 40
11-06
Zero-speed Bandwidth
0~40Hz 10
11-07
Low-speed Bandwidth
0~40Hz 10
11-08
High-speed Bandwidth
0~40Hz 10
11-09
PDFF Gain Value
0~200% 30
11-10
Gain for Speed Feed
Forward
0~500 0
11-11
Notch Filter Depth
0~20db 0
11-12
Notch Filter Frequency
0.00~200.00Hz 0.00
11-13
Low-pass Filter Time of
Keypad Display
0.001~65.535s 0.500
11-14
Motor Current at Accel.
50~200% 150
11-15
Elevator Acceleration
0.60~2.00m/s 0.75
11-16
Reserved
11-17
Reserved
11-18
Reserved