Delta Electronics VFD-VL Network Card User Manual


 
Chapter 4 Parameters|
4-4 Revision Nov. 2008, VLE1, SW V1.03
Group 1 Basic Parameters
Pr. Explanation Settings
Factory
Setting
VF
VFPG
SVC
FOCPG
TQCPG
FOCPM
01-00 Maximum Output Frequency 10.00~120.00Hz
60.00/
50.00
01-01
1st Output Frequency
Setting 1
0.00~120.00Hz
60.00/
50.00
01-02 1st Output Voltage Setting 1
230V: 0.1V~255.0V
460V: 0.1V~510.0V
220.0
440.0
01-03
2nd Output Frequency
Setting 1
0.00~120.00Hz 0.50
01-04
2nd Output Voltage Setting
1
230V: 0.1V~255.0V
460V: 0.1V~510.0V
5.0
10.0
01-05
3rd Output Frequency
Setting 1
0.00~120.00Hz 0.50
01-06
3rd Output Voltage Setting 1
230V: 0.1V~255.0V
460V: 0.1V~510.0V
5.0
10.0
01-07
4th Output Frequency
Setting 1
0.00~120.00Hz 0.00
01-08
4th Output Voltage Setting 1
230V: 0.1V~255.0V
460V: 0.1V~510.0V
0.0
0.0
01-09 Start Frequency
0.00~120.00Hz 0.50
01-10
Output Frequency Upper
Limit
0.00~120.00Hz
120.00
01-11
Output Frequency Lower
Limit
0.00~120.00Hz
0.00
01-12
Accel Time 1 0.00~600.00 sec
3.00
01-13
Decel Time 1 0.00~600.00 sec
2.00
01-14
Accel Time 2 0.00~600.00 sec
3.00
01-15
Decel Time 2 0.00~600.00 sec
2.00
01-16
Accel Time 3 0.00~600.00 sec
3.00
01-17
Decel Time 3 0.00~600.00 sec
2.00
01-18
Accel Time 4 0.00~600.00 sec
3.00
01-19
Decel Time 4
0.00~600.00 sec 2.00
01-20
JOG Acceleration Time 0.00~600.00 sec
1.00
01-21
JOG Deceleration Time 0.00~600.00 sec
1.00
01-22
JOG Frequency
0.00~120.00Hz 6.00
01-23
Switch Frequency between
1st/4th Accel/decel
0.00~120.00Hz 0.00
01-24
S-curve for Acceleration
Departure Time S1
0.00~25.00 sec 1.00
01-25
S-curve for Acceleration
Arrival Time S2
0.00~25.00 sec 1.00
01-26
S-curve for Deceleration
Departure Time S3
0.00~25.00 sec 1.00
01-27
S-curve for Deceleration
Arrival Time S4
0.00~25.00 sec 1.00
01-28
Mode Selection when
Frequency < Fmin
0: Output waiting
1: Zero-speed operation
2: Fmin (4th output frequency setting)
0
01-29
Switch Frequency for S3/S4
Changes to S5
0.00~120.00Hz 0.00
01-30
S-curve for Deceleration
Arrival Time S5
0.00~25.00 sec 1.00
01-31
Deceleration Time when
Operating without RUN
Command
0.00~60.00 sec 2.00