Delta Electronics VFD-VL Network Card User Manual


 
Chapter 4 Parameters|
Revision Nov. 2008, VLE1, SW V1.03 4-33
01-00
01-13,15,17,19
01-12,14,16,18
Frequenc
y
Time
M
ax. Output
Frequency
Frequency
Setting
accel. time decel. time
Accel./Decel. Time
01-22 JOG Frequency Unit: 0.01
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: 6.00
Settings 0.00~120.00Hz
Both external terminal JOG and key “JOG” on the keypad can be used. When the jog
command is ON, the AC motor drive will accelerate from 0Hz to jog frequency (Pr.01-22).
When the jog command is OFF, the AC motor drive will decelerate from Jog Frequency to zero.
The used Accel./Decel. time is set by the Jog Accel./Decel. time (Pr.01-20, Pr.01-21).
The JOG command can’t be executed when the AC motor drive is running. In the same way,
when the JOG command is executing, other operation commands are invalid except
forward/reverse commands and STOP key on the digital keypad.
Frequenc
y
Time
01-22
JOG frequency
01-07
4th output
frequency
setting
01-20
01-21
JOG acceleration time
JOG deceleration time
JOG accel./decel. time
01-23 Switch Frequency between 1st/4th Accel/decel Unit: 0.01
Control
mode
VF VFPG SVC FOCPG FOCPM
Factory setting: 0.00
Settings 0.00~120.00Hz