Delta Electronics VFD-VL Network Card User Manual


 
Chapter 4 Parameters|
4-10 Revision Nov. 2008, VLE1, SW V1.03
Group 5 IM Motor Parameters
Pr. Explanation Settings
Factory
Setting
VF
VFPG
SVC
FOCPG
TQCPG
FOCPM
05-00 Motor Auto Tuning 0: No function
1: Rolling test (Rs, Rr, Lm, Lx, no-load current)
2: Static Test
0
05-01 Full-load Current of Motor 40-120% #.##
05-02
Rated power of Motor 0.00~655.35kW #.##
05-03
Rated speed of Motor (rpm) 0~65535 1710
05-04 Number of Motor Poles 2~48 4
05-05 No-load Current of Motor 0-100% #.##
05-06 Rs of Motor
0.000~65.535Ω
0.000
05-07 Rr of Motor
0.000~65.535Ω
0.000
05-08 Lm of Motor 0.0~6553.5mH 0.0
05-09 Lx of Motor 0.0~6553.5mH 0.0
05-10
Torque Compensation Time
Constant
0.001~10.000sec 0.020
05-11
Slip Compensation Time
Constant
0.001~10.000sec 0.100
05-12
Torque Compensation Gain 0~10
0
05-13
Slip Compensation Gain 0.00~10.00
0.00
05-14
Slip Deviation Level 0~1000% (0: disable)
0
05-15
Detection Time of Slip
Deviation
0.0~10.0 sec 1.0
05-16
Over Slip Treatment
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
0
05-17
Hunting Gain 0~10000 (0: disable) 2000
○ ○
05-18 Accumulative Motor
Operation Time (Min.)
00~1439 00
05-19 Accumulative Motor
Operation Time (day)
00~65535 00
05-20
Core Loss Compensation 0~250% 10