Delta Electronics VFD-VL Network Card User Manual


 
Chapter 4 Parameters|
4-74 Revision Nov. 2008, VLE1, SW V1.03
06-26 PTC (Positive Temperature Coefficient) Detection Selection
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: 0
Settings 0 Warn and keep operating
1 Warn and ramp to stop
It is used to set the treatment after detecting PTC.
06-27 PTC Level Unit: 0.1
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: 50.0
Settings 0.0 to 100.0%
It is used to set the PTC level, and the corresponding value for 100% is max. analog input
value.
06-28 Filter Time for PTC Detection Unit: 0.01
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Factory setting: 0.20
Settings 0.00 to 10.00 sec
06-29 EPS Voltage Unit: 0.1
Control
mode
VF VFPG SVC FOCPG TQCPG FOCPM
Settings 48.0~375.0Vdc Factory setting: 48.0
96.0~750.0Vdc Factory setting: 96.0
It is used with the setting 43 (EPS function) of Pr.02-01~02-08 (Multi-Function Input
Command).