Delta Electronics VFD-VL Network Card User Manual


 
Chapter 4 Parameters|
Revision Nov. 2008, VLE1, SW V1.03 4-39
Control Mode
Settings
VF VFPG SVC FOCPG TQCPG FOCPM
32: Middle torque bias (by Pr.07-22)
33: Low torque bias (by Pr.07-23)
34-37: Reserved
38: Disable write EEPROM function
39: Torque command direction
40: Enable drive function
41: Reserved
42: Mechanical brake
43: EPS function
This parameter selects the functions for each multi-function terminal.
If Pr.02-00 is set to 3-wire operation control. Terminal MI1 is for STOP terminal. Therefore, MI1
is not allowed for any other operation.
Settings Functions Descriptions
0 No Function
1
Multi-step speed
command 1
2
Multi-step speed
command 2
3
Multi-step speed
command 3
4
Multi-step speed
command 4
15 step speeds could be conducted through the digital
statuses of the 4 terminals, and 17 in total if the master
speed and JOG are included. (Refer to Pr. 04-00~04-14)
5 Reset
After the error of the drive is eliminated, use this
terminal to reset the drive.
6 JOG Command JOG operation
7
Acceleration/deceleration
Speed Inhibit
When this function is enabled, acceleration and
deceleration is stopped and the AC motor drive starts
to accel./decel. from the inhibit point.
8
The 1
st
, 2
nd
acceleration
or deceleration time
selection
9
The 3
rd
, 4
th
acceleration
or deceleration time
selection
The acceleration/deceleration time of the drive could
be selected from this function or the digital statuses of
the terminals; there are 4 acceleration/deceleration
speeds in total for selection.
10 EF Input
External fault input terminal and decelerates by Pr.07-
28. (EF fault will be recorded)
11 Reserved
12 Stop output