Juniper Networks EX8208 Switch User Manual


 
NOTE: GroundingisprovidedtoanAC-poweredswitchwhenyouplugitspowersupplies
into grounded AC power receptacles.
Figure 32 on page 88 shows the cable lug that attaches to the grounding cable in an
EX8208 switch.
Figure 32: Grounding Cable Lug For an EX8208 Switch
The grounding cable that you providefor an EX8208 switchmust be 6 AWG (13.3 mm
2
),
minimum 60°C wire, or as permitted by the local code.
The grounding cable that you provide for an EX8216 switch must be 2 AWG (33.6 mm
2
),
minimum 60°C wire, or as permitted by the local code.
NOTE: Two grounding lugs for an EX8216 switch are shipped with the chassis.
WARNING: The switch is pluggable type A equipment installed in a restricted-access
location.Ithasaseparateprotectiveearthingterminalprovidedonthechassisinaddition
tothegroundingpinofthepowersupplycord.Thisseparateprotectiveearthingterminal
mustbepermanentlyconnectedtoearthgroundforinstallationsthatrequireaseparate
grounding conductor to the chassis.
Related Topics AC Power Supply in an EX8200 Switch on page 40
DC Power Supply in an EX8200 Switch on page 48
Connecting AC Power to an EX8200 Switch on page 173
Connecting DC Power to an EX8200 Switch on page 175