Table 39: Rack Requirements and Specifications for an EX8208 Switch
GuidelinesRack Requirement
Use a four-post rackor a two-postrack. Youcan mount the switchon any four-post
or two-post rackthat provides bracket holes or holepatterns spacedat1 U (1.75
in./4.44cm) incrementsand thatmeetsthesizeand strengthrequirementsspecified
in this table.
A U is the standardrackunit defined in Cabinets, Racks,Panels,and Associated
Equipment (documentnumber EIA-310–D)published by the ElectronicsIndustry
Association (http://www.eia.org).
Youcan stackthreeEX8208 switchesin afour-postrackthat hasatleast42 U; ifyou
installthe optional powercordtray,a minimum of 45 U arerequired. Youcanstack
threeEX8208 switchesin a two-postrackthathas 45 U (installingthe powercord
trayismandatoryfortwo-postrackinstallations).Inallcases,therackmustmeetthe
strengthrequirementstosupport the weight.
Racktype and mounting brackethole
spacing
Ensurethat the rack is a 19-in. rackas definedin Cabinets,Racks,Panels,and
AssociatedEquipment(documentnumberEIA-310–D)publishedbytheElectronics
Industry Association (http://www.eia.org).
Ensurethat the rack is one of the following standard lengths:
23.62in. (600mm)
30.0 in. (762mm)
21.5 in. (546 mm)
Ensurethat the rack railsare spacedwidelyenough toaccommodatethe EX8208
switch chassis'externaldimensions of 24.25in. (61.6cm) height, 17.25in. (43.815
cm)width,20in.(50.8cm)depth.Theouteredgesofthefront-mountingbrackets
extend the width to19 in. (48.3 cm).
TheEX8208 switchchassis heightof 24.25in. (61.6cm) is approximately 14 U.If
youinstallthepowercordtray(optionalforfour-postrackinstallations,mandatory
fortwo-postrackinstallations), the chassisand powercordtrayconsume 15 U.
Therackmustbestrongenoughtosupporttheweightofthefullyconfiguredswitch.
A fullyconfigured EX8208 switchweighsup to 284 lb (130 kg). Ifyou stackthree
fullyconfigured EX8208 switches in one rack,that rackmust support up to852 lb
(487 kg).
Ensurethat the spacingof railsand adjacentracksallows forthe proper clearance
aroundtheswitchandrackasspecifiedin“ClearanceRequirementsforAirflowand
Hardware Maintenance foran EX8208 Switch” on page101.
Racksize and strength
Secure the racktothe building structure.
If earthquakes area possibility in yourgeographical area,securethe rack tothe
floor.
Securetheracktotheceilingbracketsaswellaswallorfloorbracketsformaximum
stability.
Rackconnectiontothe building
structure
Copyright ©2010,Juniper Networks,Inc.98